Technicial Specifications
| Standby Rating | 3000 kVA (3100 kVA without fan) | 
| Prime Power Rating | 2750 kVA (2850 kVA without fan) | 
| Emissions/Fuel Strategy | Low Fuel Consumption | 
| Voltage | 380 to 11000 volts | 
| Frequency | 50 Hz | 
| Speed | 1500 rpm | 
| Duty Cycle | Standby, Mission Critical, Prime | 
| Maximum Rating | 3000 kVA (3100 kVA without fan) | 
| Minimum Rating | 2750 kVA (2850 kVA without fan) | 
| Engine Model | 3516E, SCAC, V-16, 4-Stroke, Water-Cooled Diesel | 
| Bore | 170 mm | 
| Stroke | 215 mm | 
| Displacement | 78.1 l | 
| Compression Ratio | 14:01 | 
| Aspiration | TA | 
| Fuel System | Electronic unit injection | 
| Governor Type | Adem™ A5 | 
| Length - Maximum | 7538 mm | 
| Width - Maximum | 2216 mm | 
| Height - Maximum | 3391 mm | 
| Dry Weight - Genset (maximum) | 19750 kg | 
Advantages and Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
 - Accepts 100% block load in one step and meets NFPA 110 loading requirements
 - Conform to ISO 8528-5 steady state and transient response requirements
 
Cat Diesel Engine
- Reliable, rugged, durable design
 - Field-proven in thousands of applications worldwide
 - Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
 
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
 - Designed to match performance and output characteristics of Cat diesel engines
 - Robust Class H insulation
 
EMCP 4 Control Panel
- User-friendly interface and navigation
 - Scalable system to meet a wide range of installation requirement
 - Expansion modules and site-specific programming for specific customer requirements
 
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
 - Contact your Cat Dealer for specific ambient and altitude capabilities
 
Certifications
- EU Declaration of Conformity
 - EU Declaration of Incorporation
 - Eurasian Conformity (EAC)
 - Telecommunication Lab of China
 
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
 - The generator set is fully assembled at a Caterpillar facility following our quality guidelines
 - Each generator set package is tested before leaving the Caterpillar facility
 - Cat product support, including dealer service, parts and warranty covers the entire Cat power system
 
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
 - Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
 
Standard Equipment
- 
                        Air Inlet System
                        
                        
                        
- Air cleaner
 
- Single element canister type with service indicator
 
 
- 
                        Control Panel
                        
                        
                        
- Environmental sealed front face
 
- Warning/shutdown with common LED indication of shutdowns for:
 
- Overspeed
 
- RPM
 
- Generator phase sequence
 
- Emergency stop pushbutton
 
- Digital indication for:
 
- Text alarm/event descriptions
 
- 2 Programmable digital outputs
 
- Reverse reactive power (kVAr) (32RV)
 
- Reverse power (kW) (32)
 
- Failure to start (overcrank)
 
- Panel lights
 
- Speed adjust
 
- Oil pressure (psi, kPa or bar)
 
- Low coolant level
 
- Generator mounted - rear facing
 
- Over/under frequency (81 o/u)
 
- Lamp test
 
- True RMS AC metering, 3-phase, +/-2% accuracy
 
- Low coolant temperature
 
- Power factor (per phase & average)
 
- Frequency (Hz)
 
- Overcurrent (50/51)
 
- High coolant temperature
 
- DC volts
 
- 6 Programmable digital inputs
 
- Coolant temperature
 
- 24 Volt DC operation
 
- Amps (per phase & average)
 
- Emergency stop
 
- Alarm acknowledge
 
- Programmable protective relaying functions:
 
- 2 Programmable relay outputs (Form C)
 
- EMCP 4.2B
 
- Serial annunciator module data link
 
- Controls:
 
- kW-hr (total)
 
- kW (per phase, average & percent)
 
- Engine cool-down timer
 
- Operating hours
 
- EMCP 4 Genset controller
 
- Volts (L-L & L-N)
 
- Engine cycle crank
 
- Communications:
 
- kVAr (per phase, average & percent)
 
- EMCP4.2B controller includes:
 
- Customer data link (Modbus RTU)
 
- Over/under voltage (27/59)
 
- Low oil pressure
 
- kVA (per phase, average & percent)
 
- kVAr-hr (total)
 
- 4 Programmable relay outputs (Form A)
 
- Accessory module data link
 
 
- 
                        Exhaust
                        
                        
- Exhaust flange outlet
 
 
- 
                        Fuel
                        
                        
- Primary fuel filter with integral water separator
 
 
- 
                        Generator
                        
                        
                        
- IP23 Protection
 
- Matched to the performance and output characteristics of Cat engines
 
 
- 
                        Power Termination
                        
                        
- Busbar
 
 
- 
                        Starting/Charging
                        
                        
                        
- Heavy duty starting system
 
- Charging alternator
 
 
- 
                        Cooling System
                        
                        
                        
- Caterpillar extended life coolant
 
- Radiator fan and fan drive
 
- Fan and belt guards
 
- JWAC
 
- Coolant drain line with valve
 
- Coolant level sensors
 
 
- 
                        Cooling
                        
                        
- Package mounted radiator
 
 
- 
                        Exhaust System
                        
                        
                        
- Dry exhaust manifold
 
- Flanged faced outlet(s)
 
 
- 
                        Fuel System
                        
                        
                        
- Secondary fuel filters
 
- Fuel priming pump
 
- Fuel cooler; not included with packages without radiator
 
- Flexible fuel lines - shipped loose
 
 
- 
                        Generators and Attachments
                        
                        
                        
- Internal excitation (IE)
 
- 6 Lead
 
- Busbar connections, top center mounted, top cable entry
 
- IEC standard hole pattern
 
- Random wound
 
- 3 Phase brushless, Salient pole
 
- Winding temperature detectors
 
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby).
 
- Generator set packages include Caterpillar's digital voltage regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
 
 
- 
                        Governing System
                        
                        
- ADEM III
 
 
- 
                        Literature
                        
                        
- Parts book
 
 
- 
                        Lube System
                        
                        
                        
- Lubricating oil
 
- Oil filter, filler and dipstick
 
- Fumes disposal
 
- Oil drain lines and valve
 
- Gear type lube oil pump
 
- Integral lube Oil cooler
 
 
- 
                        Mounting System
                        
                        
                        
- Rubber anti-vibration mounts - shipped loose
 
- Rails - Engine/generator/radiator mounting
 
 
- 
                        Starting / Charging System
                        
                        
                        
- Battery and battery rack w/cables
 
- 24 Volt electric starting motor
 
- Battery disconnect switch
 
 
- 
                        General
                        
                        
                        
- Right hand servicing
 
- Paint - Caterpillar yellow with high gloss black rails & radiator
 
- Flywheel and flywheel housing-SAE No. 00
 
- SAE standard rotation
 
 
Optional Equipment
- 
                        Air Inlet System
                        
                        
                        
- Air inlet protection
 
- Heavy duty air cleaners
 
- Remote air inlet adapters
 
- Dual element air cleaners
 
 
- 
                        Circuit breakers
                        
                        
                        
- Cable entry options
 
- Control packaging for enclosures
 
- Optional busbar power connections
 
- EMAX breakers
 
- Load take off; IEC standard hole
 
- Center posts busbars
 
- Trip units
 
 
- 
                        Power Termination
                        
                        
- Circuit breakers, IEC compliant
 
 
- 
                        Control Panels
                        
                        
                        
- External box clips
 
- Local and remote monitoring
 
- Busbar connections
 
- Governors
 
- Generator temperature monitoring
 
- Auxiliary box
 
- Voltage raise/lower switch
 
- EMCP 4.3, EMCP 4.4
 
- EMAX breaker connections
 
- Language options
 
- Remote speed adjust
 
- Annunciator modules
 
- Customer interface options
 
- Vandal proof panel door
 
 
- 
                        Cooling System
                        
                        
                        
- Optional Serpentine radiators
 
- Water level switch gauges
 
- Heat exchangers
 
- Radiator duct flanges
 
 
- 
                        European Certifications
                        
                        
- EU Declaration of Conformity
 
 
- 
                        Exhaust System
                        
                        
                        
- Mufflers
 
- Through wall installation kit
 
- Flexible fittings
 
- Muffler mounting kits
 
 
- 
                        Fuel System
                        
                        
                        
- Fuel coolers
 
- Primary fuel filter
 
 
- 
                        Generators and attachments
                        
                        
                        
- 3 Phase, Random wound, Internal excitation (IE)
 
- Internal excitation (IE)
 
- Random wound
 
- Pitch: 0.6667
 
- Optional generators
 
- Number of leads: 6
 
- 
                            3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
 
 
- 
                        Instrumentation
                        
                        
                        
- Thermocouples
 
- Pyrometers and thermocouples
 
 
- 
                        Lube System
                        
                        
                        
- Manual prelube sump pumps
 
- Oil level regulator
 
- Electric prelube pumps
 
 
- 
                        Mounting System
                        
                        
                        
- Spring type vibration isolators
 
- IBC vibration isolators
 
 
- 
                        Protection System
                        
                        
- Explosion relief valves
 
 
- 
                        Special Tests / Reports
                        
                        
                        
- PGS Test report @ 0.8 power factor
 
- CSA test and certification
 
- Neutral ground certificate
 
- PGS Test report @ 1.0 power factor
 
- IBC seismic Certification
 
 
- 
                        Starting / Charging System
                        
                        
                        
- Jacket water heaters
 
- ETHER starting aids
 
- Dual 24 volt electric starting motors
 
- 24 Volt battery set - Dry
 
- Charging alternators - 50 Amp
 
- 10 and 20 Amp Battery chargers
 
 
- 
                        General
                        
                        
- Engine barring group