Технические характеристики
Continuous Rating | 4300 / 4000 ekW @1.0pf |
Fuel Type | Natural Gas, Biogas, Coal Gas, Associated Gas, Synthesis Gas, Hydrogen Blend (to 25%) |
Maximum Electrical Efficiency | 44.1 / 43.8% |
Maximum Standby Rating | 4500 ekW |
Frequency | 50 / 60 Hz |
RPM | 1000 / 900 rpm |
Engine Model | CG260-16 |
Displacement | 271.8 l |
Aspiration | TA |
Bore | 260 mm |
Stroke | 320 mm |
Length | 9420 mm |
Width | 2794 mm |
Height | 3390 mm |
Dry Weight - Genset | 53299.4 kg |
Преимущества и особенности
High Reliability
- Anti-knock control and cylinder balancing protect the engine from overload and ensure reliable operation
- State-of-the-art turbocharger A140 with Wastegate ensures full performance even under high temperatures and higher altitudes
- Higher reliability and lower maintenance costs due to open combustion chamber technology
High Availability, High Profitability
- Miller valve timing and optimized compression ratios ensure high efficiency and low fuels costs
- More profit for your plant
- Long maintenance intervals and general overhaul only after 80,000 oh allow an operation of 10 years without general overhaul
- Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
Optimized Lubrication Consumption
- Savings of up to 4,000 liters of lube oil per year compared to comparable gensets
- Improved components reduce lube oil consumption
- Lower operating costs due to 30% lower lube oil consumption in comparison to similar products
Стандартное оборудование
-
Air Inlet
- One-element single-stage air cleaner with enclosure and sevice indicator
- Turbocharger with a water-cooled bearing case for all cylinder
-
Control Panels
- TEM (Total Electronic Management)
-
Cooling
- flange connections for JW inlet and outlet
- Jacket water and SCAC thermostats
- Electrical jacket water and aftercooler coolant pump
-
Exhaust
- Exhaust waste gate for the CG260-16
- Closed crankcase ventilation system
-
Fuel system
- Electronic fuel metering valve
- Independently controlled cylinder monitoring and ignition system
- Pre-chamber spark plugs
-
Generator
- Busbar connections
- Closed-coupled generator result in no torque transmission to the base frame
- Reactive droop
- 3-phase sensing and KVAR/PF control
- Grid code generator
- Anti-condensation space heater
- Winding temperature detectors
-
Starting/Charging
- Compressed air engine start
-
General
- Crankshaft vibration damper and guard
Дополнительное оборудование
-
Cooling
- CHP skid
-
Grid Code Compliance
- 50Hz: Germany, Belgium, Great Britain, Italy, Poland, and Netherlands